CIRCULAR CHART RECORDERS

202.jpg
FEATURES:
  • Accepts any powered analog signal or temperature input
  • Quick and easy setup– even without a manual
  • Uses standard, brand name chart paper
  • Built in backup battery provides up to 48 hrs of recording during power loss
  • Self documents your setup for future reference
  • Optional transmitter power supply
  • UL, CUL, CE
Rating
0 vote
Favoured:
0

Listing Details

Product Description
The CR500, Circular Chart Recorder, with a water level sensor.
The Global Water CR500 series circular chart recorders provide reliable, accurate records for your analog and temperature data.  The circular chart recorder's universal configurable input(s) will accept virtually any type of thermocouple, RTD, 4-20mA, or analog sensors.  With its easy to use, self documenting configuration chart, the circular chart recorder provides quick and trouble-free programming.  The circular chart recorders also let you save money and avoid confusion by using standard 10 inch Honeywell® or Partlow® chart paper. To protect your process information, the CR500 circular chart recorders come standard with a battery backup option, which provides continuous recording for up to 48 hours in the event of power loss.  The circular chart recorders are not recommended for outdoor use due to possible paper damage.  Choose our optional built-in transmitter power supply to power virtually any analog sensor, including pressure, level, pH, flow, or any number of other sensors, directly from the circular chart recorders. Choose from standard one- or two-pen units and circular paper chart recorders with programmable alarm relay outputs.  Each of paper.  See our selection of replacement chart paper in the Options & Ordering section. Call or email us for these available nonstock circular chart recorder options: LED process display, NEMA 4 enclosure, direction of our CR500 circular chart recorders includes chart pen(s), a 9 VDC backup battery, configuration charts, and a box of starter chart rotation.
Specification
Circular Chart Recorders Power
Line Voltage: 110/220VAC, 50/60Hz
Power Consumption: 15VA maximum
Battery Backup: Standard 9 volt, up to 48 hours of operation
Error Protection: De-energized during sensor break
NOTE: The CR500 circular chart recorders are not recommended for use in remote non-powered areas. Circular Chart Recorders Inputs
Thermocouple (T/C)
Type J, K, T, R, B, S, RTD: PT 100 ohm RTD (385 curve)
Linear: 4-20 mA
Range: Per table in manual
Common Mode Rejection: > 120dB at 60 Hz
Cold Junction Accuracy: ± 0.2°C @ 25°C ambient
Ambient Error: ± 0.01% span/°C from 25°C ambient
Isolation: Inputs share common ground on 2-pen units
Input: Impedance Linear = 249 ohm, TC = 470Kohm Circular Chart Recorders Recording
Chart Size: 10"
Recording Accuracy: ± 0.5% of span (100 division span)
Recording Error: ± 5% of span
Recording Repeatability: ± 1%
Sensor Break: Full scale pen < 10 seconds
Chart Speed: Configurable
Input Filtering: Programmable up to 120 seconds Circular Chart Recorders Environmental & Physical
Operating Temperature: 0 to 60°C
Storage Temperature: -40 to 65°C
Humidity: 0-90% RH (non-condensing)
Vibration: 0.3 to 100Hz @ 0.2g
Mounting: ± 20 degrees of vertical, ± 10 degrees of horizontal
Moldings: Fire retardant Noryl w/acrylic window
Panel Rating: Nema 3 std (Nema4 option)
Dimensions: 14.0" (H) x 14.0" (W) x 3.8" (D)
Panel Cutout: Industry Standard 12.7" x 12.7"
Weight: 7 pounds maximum Circular Chart Recorder Relays (Optional)
Relay: DPDT, 1.0 Amps @ 120 VAC resistive
Relay Program: Process, Band, Non-latching, Latching
Hysteresis: Set at 2 units, activation is safe sided Circular Chart Recorder Powered Sensor Option
Transmitter Power Supply: 12VDC @ 1.0A